Lead Testing
The Oregon Health Authority's Healthy and Safe Schools (HASS) Plan promotes transparency around lead in water testing by school districts, ESDs, and charter schools. Lead in water testing is required by Division 22 Rules (OAR 581-022-2223). All school districts, ESDs, and charter schools must test all required fixtures for elevated levels of lead at least every 6 years starting July 1, 2020 per OAR 333-061-0400. The basic schedule for when testing is to occur is set by the Oregon Department of Education (ODE), with specific facility test times for districts testing over multiple years to be determined cooperatively between ODE and the district.
The lead in water testing process, though not complicated, involves many steps. The high level overview process is: Fixture ID & Sample ID Numbers, Selecting a Lab, Water Sampling, Lead in Water Testing at Lab, Elevated Lead Levels & Remediation, Reproting Test Results, Reimbursement, and Certification.
The state will reimburse school districts, charter schools, and ESDs for the direct lab costs associated with mandatory testing of water for elevated levels of lead. This includes reimbursement for the lab costs, as well as other qualifying expenses such as sample bottles and shipping costs. In addition, ODE will reimburse a set amount on a per sample basis in an attempt to help offset collection costs. These funds can also be used to help offset costs paid to consultants for districts that have chosen to hire outside companies to perform this work for them. The additional per sample amount will be determined largely on the availability of funds once all direct lab costs for the state have been paid for a given year. Reimbursement requires submission of properly completed reimbursement form templates, lab results, lab invoices, and receipts.
2024-25 Testing
-
On October 3, 2024, PBS Engineering and Environmental Inc. (PBS) performed drinking water sampling and analysis for lead at Fairview Elementary School in Fairview, Oregon. The testing was requested by Reynolds School District to meet requirements from the Oregon Department of Education (ODE) and Oregon Health Authority (OHA) to conduct testing for lead in school drinking water systems.
Lead in Water Test Notes
- The lead in water Action Level is 15 parts per billion (ppb).
- Any fixture testing at or above the action level of 15 ppb is immediately removed from service and cannot be returned to service until it has been remediated and passed follow-up testing.
- A "ND" or "non-detect" test result indicates no lead.
- Test results equal to or greater than the Action Level of 15 ppb are highlighted in red and precede a "Action Required" value.
- Test results near the Action Level of 15 ppb (12 to 14.99 ppb) are highlighted in orange and precede a "High" value.
Initial Test Results
Lead in Water Test Results Summary
Fixture Location Description Fixture ID # Initial
Test DateInitial Test Result (ppb) Initial
LevelKitchen, South dishwashing sink faucet, left 001 10/3/24 7.49 Low Kitchen, South dishwashing sink faucet, right 002 10/3/24 1.65 Low Kitchen, South hand wash sink faucet 003 10/3/24 0.886 Low Kitchen, North food prep sink faucet 004 10/3/24 0.339 Low Kitchen, North handwash sink 005 10/3/24 0.255 Low Kitchen, staff restroom 129, bathroom faucet 006 10/3/24 ND Non-Detect Cafeteria, West end handwash sink faucet 007 10/3/24 ND Non-Detect Restroom 122, left faucet 008 10/3/24 ND Non-Detect Restroom 122, right faucet 009 10/3/24 0.258 Low Restroom 123, left faucet 010 10/3/24 0.465 Low Restroom 123, right faucet 011 10/3/24 0.290 Low Restroom 113, bathroom faucet 012 10/3/24 0.306 Low Restroom 104, bathroom faucet 013 10/3/24 ND Non-Detect Staff room 105, staff faucet 014 10/3/24 7.28 Low Staff lounge 107, Northwest staff faucet 015 10/3/24 ND Non-Detect Staff lounge 107, Southeast staff faucet 016 10/3/24 0.290 Low Nurse office 101, nurse faucet 017 10/3/24 0.481 Low Nurse office 101, bathroom faucet 018 10/3/24 ND Non-Detect Gym, South wall, water bottle filler 019 10/3/24 ND Non-Detect Gym, South staff restroom 120 D 020 10/3/24 6.78 Low Room 114, South sink, classroom faucet, left 021 10/3/24 8.31 Moderate Room 114, South sink, classroom faucet, right 022 10/3/24 15.2 Action Req. Room 14. West sink, classroom faucet 023 10/3/24 ND Non-Detect Room 140, drinking fountain 024 10/3/24 5.45 Low Room 140, classroom faucet 025 10/3/24 0.643 Low Room 140, water bottle filler 026 10/3/24 ND Non-Detect Restroom 140B, bathroom faucet 027 10/3/24 0.301 Low Room 141, left sink, drink fountain 028 10/3/24 0.551 Low Room 141, left sink, classroom faucet 029 10/3/24 2.67 Low Room 141, right sink, drink fountain 030 10/3/24 0.374 Low Room 141, right sink, classroom faucet 031 10/3/24 0.390 Low Room 141A, bathroom faucet 032 10/3/24 11.7 Moderate Room 142, left sink, drink fountain 033 10/3/24 0.506 Low Room 142, left sink, classroom faucet 034 10/3/24 ND Non-Detect Room 142, right sink, drink fountain 035 10/3/24 0.661 Low Room 142, right sink, classroom faucet 036 10/3/24 0.330 Low Room 142A, bathroom faucet 037 10/3/24 0.239 Low Room 143, left sink, drink fountain 038 10/3/24 0.814 Low Room 143, left sink, classroom faucet 039 10/3/24 0.235 Low Room 143, right sink, drink fountain 040 10/3/24 0.500 Low Room 143, right sink, classroom faucet 041 10/3/24 ND Non-Detect Room 143A, bathroom faucet 042 10/3/24 ND Non-Detect Room 144, left sink, drink fountain 043 10/3/24 3.05 Low Room 144, left sink, classroom faucet 044 10/3/24 0.214 Low Room 144, right sink, drink fountain 045 10/3/24 3.32 Low Room 144, right sink, classroom faucet 046 10/3/24 ND Non-Detect Restroom 144B, East restroom, bathroom faucet 047 10/3/24 0.309 Low Restroom 144B, West restroom, bathroom faucet 048 10/3/24 0.620 Low Restroom 160B 049 10/3/24 ND Non-Detect Room 164, drink fountain 050 10/3/24 0.301 Low Room 164, classroom faucet 051 10/3/24 ND Non-Detect Room 163, drink fountain 052 10/3/24 0.424 Low Room 163, classroom faucet 053 10/3/24 ND Non-Detect Room 160, classroom faucet 054 10/3/24 ND Non-Detect Room 160, water bottle filler 055 10/3/24 ND Non-Detect Room 162, drink fountain 056 10/3/24 0.254 Low Room 162, classroom faucet 057 10/3/24 ND Non-Detect Room 161, drink fountain 058 10/3/24 0.612 Low Room 161, classroom faucet 059 10/3/24 ND Non-Detect Restroom 144, left sink, left faucet 060 10/3/24 0.217 Low Restroom 144, left sink, right faucet 061 10/3/24 0.317 Low Restroom 145, left sink, left faucet 062 10/3/24 0.675 Low Restroom 145, left sink, right faucet 063 10/3/24 ND Non-Detect Restroom 150B, bathroom faucet 064 10/3/24 ND Non-Detect Room 154, drink fountain 065 10/3/24 0.594 Low Room 154, classroom faucet 066 10/3/24 0.302 Low Room 153, drink fountain 067 10/3/24 0.205 Low Room 153, classroom faucet 068 10/3/24 ND Non-Detect Room 150, classroom faucet 069 10/3/24 ND Non-Detect Room 150, water bottle filler 070 10/3/24 ND Non-Detect Room 152, drink fountain 071 10/3/24 7.19 Low Room 152, classroom faucet 072 10/3/24 ND Non-Detect Room 151, drink fountain 073 10/3/24 0.264 Low Room 151, classroom faucet 074 10/3/24 ND Non-Detect Restroom 154, bathroom faucet, left 075 10/3/24 0.204 Low Restroom 154, bathroom faucet, right 076 10/3/24 0.285 Low Restroom 155, bathroom faucet, left 077 10/3/24 0.388 Low Restroom 155, bathroom faucet, right 078 10/3/24 0.261 Low Restroom 240B, bathroom faucet 079 10/3/24 ND Non-Detect Room 244, left sink 080 10/3/24 Not Tested - Room 244, left sink 081 10/3/24 Not Tested - Room 244, right sink 082 10/3/24 Not Tested - Room 244, right sink 083 10/3/24 Not Tested - Restroom 244A, bathroom faucet 084 10/3/24 0.551 Low Room 243, drink fountain 085 10/3/24 0.257 Low Room 243, classroom faucet 086 10/3/24 ND Non-Detect Room 240, classroom faucet 087 10/3/24 0.294 Low Room 240, water bottle filler 088 10/3/24 ND Non-Detect Room 242, drink fountain 089 10/3/24 0.492 Low Room 242, classroom faucet 090 10/3/24 ND Non-Detect Room 241, drink fountain 091 10/3/24 2.31 Low Room 241, classroom faucet 092 10/3/24 1.24 Low Restroom 246, bathroom faucet, left 093 10/3/24 0.261 Low Restroom 246, bathroom faucet, right 094 10/3/24 0.466 Low Restroom 245, bathroom faucet, left 095 10/3/24 0.873 Low Restroom 245, bathroom faucet, right 096 10/3/24 0.323 Low Restroom 260B, bathroom faucet 097 10/3/24 ND Non-Detect Room 263, drink fountain 098 10/3/24 0.776 Low Room 263, classroom faucet 099 10/3/24 0.344 Low Room 260, classroom faucet 100 10/3/24 0.222 Low Room 260, Water bottle filler 101 10/3/24 ND Non-Detect Room 262, drink fountain 102 10/3/24 ND Non-Detect Room 262, classroom faucet 103 10/3/24 0.395 Low Room 261, drink fountain 104 10/3/24 ND Non-Detect Room 261, classroom faucet 105 10/3/24 ND Non-Detect Restroom 266, bathroom faucet, left 106 10/3/24 0.386 Low Restroom 266, bathroom faucet, right 107 10/3/24 0.558 Low Restroom 265, bathroom faucet, left 108 10/3/24 0.258 Low Restroom 265, bathroom faucet, right 109 10/3/24 Not Tested - Restroom 250B, bathroom faucet 110 10/3/24 ND Non-Detect Room 254, drink fountain 111 10/3/24 0.419 Low Room 254, classroom faucet 112 10/3/24 0.214 Low Room 253, drink fountain 113 10/3/24 1.46 Low Room 253, classroom faucet 114 10/3/24 ND Non-Detect Room 250, classroom faucet 115 10/3/24 0.336 Low Room 250, water bottle filler 116 10/3/24 ND Non-Detect Room 252, drink fountain 117 10/3/24 0.211 Low Room 252, classroom faucet 118 10/3/24 Not Tested - Room 251, drink fountain 119 10/3/24 0.488 Low Room 251, classroom faucet 120 10/3/24 ND Non-Detect Restroom 256, bathroom faucet, left 121 10/3/24 ND Non-Detect Restroom 256, bathroom faucet, right 122 10/3/24 0.730 Low Restroom 255, bathroom faucet, left 123 10/3/24 0.271 Low Restroom 255, bathroom faucet, right 124 10/3/24 0.253 Low Room 126, drink fountain 125 10/3/24 0.445 Low Room 126, classroom faucet 126 10/3/24 ND Non-Detect Fixtures Not Sampled
The fixtures listed above as “Not Tested” could not be sampled by PBS, as they were either shut off or inaccessible. PBS assigned them a number in sequence so they can be sampled later if they are brought back online.
-
On October 2, 2024, PBS Engineering and Environmental Inc. (PBS) performed drinking water sampling and analysis for lead at Glenfair Elementary School in Portland, Oregon. The testing was requested by Reynolds School District to meet requirements from the Oregon Department of Education (ODE) and Oregon Health Authority (OHA) to conduct testing for lead in school drinking water systems.
Lead in Water Test Notes
- The lead in water Action Level is 15 parts per billion (ppb).
- Any fixture testing at or above the action level of 15 ppb is immediately removed from service and cannot be returned to service until it has been remediated and passed follow-up testing.
- A "ND" or "non-detect" test result indicates no lead.
- Test results equal to or greater than the Action Level of 15 ppb are highlighted in red and precede a "Action Required" value.
- Test results near the Action Level of 15 ppb (12 to 14.99 ppb) are highlighted in orange and precede a "High" value.
Test Results
Fixture Location Description Fixture ID # Initial
Test DateInitial Test Result (ppb) Initial
LevelFinal
Retest DateFinal Test Result (ppb) Final
LevelEast hall girl's restroom 043 5/1/23 Not Tested - 9/1/24 0.56 Low East hall, west drinking fountain 047 5/1/23 Not Tested - 9/1/2024 ND Non-Detect -
On October 4, 2024, PBS Engineering and Environmental Inc. (PBS) performed drinking water sampling and analysis for lead at Troutdale Elementary School in Troutdale, Oregon. The testing was requested by Reynolds School District to meet requirements from the Oregon Department of Education (ODE) and Oregon Health Authority (OHA) to conduct testing for lead in school drinking water systems.
Lead in Water Test Notes
- The lead in water Action Level is 15 parts per billion (ppb).
- Any fixture testing at or above the action level of 15 ppb is immediately removed from service and cannot be returned to service until it has been remediated and passed follow-up testing.
- A "ND" or "non-detect" test result indicates no lead.
- Test results equal to or greater than the Action Level of 15 ppb are highlighted in red and precede a "Action Required" value.
- Test results near the Action Level of 15 ppb (12 to 14.99 ppb) are highlighted in orange and precede a "High" value.
Test Results
Fixture Location Description Fixture ID # Initial
Test DateInitial Test Result (ppb) Initial
LevelKitchen, Northeast hand wash sink faucet 001 9/4/24 1.69 Low Kitchen, Food pre sink faucet, left 002 9/4/24 1.07 Low Kitchen, Food pre sink faucet, right 003 9/4/24 0.490 Low Kitchen, Northwest hand wash sink faucet 004 9/4/24 ND Non-Detect Kitchen, West food pre sink faucet 005 9/4/24 ND Non-Detect Staff restroom 131A, bathroom faucet 006 9/4/24 0.279 Low Cafeteria, hand wash sink faucet 007 9/4/24 1.78 Low Cafeteria, boys restroom, bathroom faucet, left 008 9/4/24 0.304 Low Cafeteria, boys restroom, bathroom faucet, right 009 9/4/24 0.306 Low Cafeteria, girls restroom, bathroom faucet, left 010 9/4/24 0.550 Low Music classroom, drinking water fountain 012 9/4/24 0.253 Low Music classroom, classroom faucet 013 9/4/24 1.14 Low Gym, water bottle filler 014 9/4/24 ND Non-Detect Gym, Southeast restroom, bathroom faucet 015 9/4/24 0.282 Low Health room, Northeast nurse faucet 016 9/4/24 ND Non-Detect Health room, restroom, bathroom faucet 017 9/4/24 ND Non-Detect Restroom 100A, bathroom faucet 018 9/4/24 ND Non-Detect Restroom 106, bathroom faucet 019 9/4/24 0.481 Low Sandy lounge 107, east sink, staff faucet, left 020 9/4/24 0.382 Low Sandy lounge 107, east sink, staff faucet, right 021 9/4/24 ND Non-Detect Sandy lounge 107, northwest sink, staff faucet 022 9/4/24 ND Non-Detect Room 140, drinking fountain 023 9/4/24 0.985 Low Room 140, classroom faucet 024 9/4/24 0.476 Low Room 141, left sink, drinking fountain 025 9/4/24 1.50 Low Room 141, left sink, classroom faucet 026 9/4/24 0.534 Low Room 141, right sink, drinking fountain 027 9/4/24 0.616 Low Room 141, right sink, classroom faucet 028 9/4/24 0.508 Low Restroom 141A, bathroom faucet 029 9/4/24 0.257 Low Room 142, left sink, drinking fountain 031 9/4/24 0.530 Low Room 142, left sink, classroom faucet 032 9/4/24 0.584 Low Room 142, right sink, drinking fountain 033 9/4/24 0.825 Low Room 142, right sink, classroom faucet 034 9/4/24 0.645 Low Restroom 142A, bathroom faucet 035 9/4/24 0.282 Low Room 143, left sink, drinking fountain 036 9/4/24 0.588 Low Room 143, left sink, classroom faucet 037 9/4/24 0.621 Low Room 143, right sink, drinking fountain 038 9/4/24 0.368 Low Room 143, right sink, classroom faucet 039 9/4/24 ND Non-Detect Restroom 143A, bathroom faucet 040 9/4/24 ND Non-Detect Room 140, water bottle filler 041 9/4/24 1.77 Low Room 144, left sink, drinking fountain 042 9/4/24 7.49 Low Room 144, left sink, classroom faucet 043 9/4/24 25.8 Action Req. Room 144, right sink, drinking fountain 044 9/4/24 1.63 Low Room 144, right sink, classroom faucet 045 9/4/24 7.73 Low Restroom 144, bathroom faucet 046 9/4/24 ND Non-Detect Restroom 140B, bathroom faucet 047 9/4/24 0.207 Low Staff restroom 150B, bathroom faucet 048 9/4/24 ND Non-Detect Room 151, classroom sink, drinking fountain 049 9/4/24 ND Non-Detect Room 151, classroom sink, classroom faucet 050 9/4/24 ND Non-Detect Room 152, classroom sink, classroom faucet 052 9/4/24 1.88 Low Room 150, classroom faucet 053 9/4/24 ND Non-Detect Room 150, water bottle filler 054 9/4/24 ND Non-Detect Room 153, classroom sink, drinking fountain 055 9/4/24 0.426 Low Room 153, classroom sink, classroom faucet 056 9/4/24 ND Non-Detect Room 154, classroom sink, classroom faucet 058 9/4/24 0.792 Low Boys restroom, left sink, bathroom faucet, left, out of room 154 059 9/4/24 0.313 Low Boys restroom, left sink, bathroom faucet, right, out of room 154 060 9/4/24 0.311 Low Girls restroom, left sink, bathroom faucet, left, out of room 154 061 9/4/24 ND Non-Detect Girls restroom, left sink, bathroom faucet, right, out of room 154 062 9/4/24 0.315 Low Staff restroom 160B, bathroom faucet 063 9/4/24 ND Non-Detect Room 161, classroom sink, drinking fountain 064 9/4/24 0.221 Low Room 161, classroom sink, classroom faucet 065 9/4/24 ND Non-Detect Room 162, classroom sink, drinking fountain 066 9/4/24 0.285 Low Room 162, classroom sink, classroom faucet 067 9/4/24 ND Non-Detect Room 160, classroom faucet 068 9/4/24 ND Non-Detect Room 160, water bottle filler 069 9/4/24 ND Non-Detect Room 163, classroom sink, drinking fountain 070 9/4/24 ND Non-Detect Room 163, classroom sink, classroom faucet 071 9/4/24 ND Non-Detect Room 164, classroom sink, drinking fountain 072 9/4/24 1.61 Low Room 164, classroom sink, classroom faucet 073 9/4/24 ND Non-Detect Boys restroom, bathroom faucet, left, out of room 164 074 9/4/24 0.227 Low Boys restroom, bathroom faucet, right, out of room 164 075 9/4/24 0.440 Low Girls restroom, bathroom faucet, left, out of room 164 076 9/4/24 ND Non-Detect Girls restroom, bathroom faucet, right, out of room 164 077 9/4/24 ND Non-Detect Second floor, staff restroom 240B, bathroom faucet 078 9/4/24 ND Non-Detect Second floor, room 241, drinking fountain 079 9/4/24 0.325 Low Second floor, room 241, classroom faucet 080 9/4/24 ND Non-Detect Second floor, room 242, drinking fountain 081 9/4/24 ND Non-Detect Second floor, room 242, classroom faucet 082 9/4/24 ND Non-Detect Second floor, Room 240, classroom faucet 083 9/4/24 0.244 Low Second floor, Room 240, water bottle filler 084 9/4/24 ND Non-Detect Second floor, room 243, drinking fountain 085 9/4/24 0.482 Low Second floor, room 243, classroom faucet 086 9/4/24 0.266 Low Second floor, Room 244, left sink, drinking fountain 087 9/4/24 2.44 Low Second floor, Room 244, left sink, classroom faucet 088 9/4/24 0.568 Low Second floor, Room 244, right sink, drinking fountain 089 9/4/24 1.36 Low Second floor, Room 244, right sink, classroom faucet 090 9/4/24 ND Non-Detect Second floor, Boys restroom, bathroom faucet, left, out of room 244 092 9/4/24 ND Non-Detect Second floor, Boys restroom, bathroom faucet, right, out of room 244 093 9/4/24 ND Non-Detect Second floor, Girls restroom, bathroom faucet, left, out of room 244 094 9/4/24 0.208 Low Second floor, Girls restroom, bathroom faucet, right, out of room 244 095 9/4/24 0.358 Low Second floor, Copy room 208, staff faucet 096 9/4/24 0.223 Low Second floor, Staff lounge, east sink, staff faucet 097 9/4/24 ND Non-Detect Second floor, Staff lounge, west sink, staff faucet 098 9/4/24 ND Non-Detect Second floor, Staff restroom, bathroom faucet 099 9/4/24 0.336 Low Second floor, room 251, drinking fountain 100 9/4/24 0.497 Low Second floor, room 251, classroom faucet 101 9/4/24 0.202 Low Second floor, room 252, drinking fountain 102 9/4/24 ND Non-Detect Second floor, room 252, classroom faucet 103 9/4/24 ND Non-Detect Second floor, room 250, classroom faucet 104 9/4/24 0.266 Low Second floor, room 250, water bottle filler 105 9/4/24 ND Non-Detect Second floor, room 253, drinking fountain 106 9/4/24 ND Non-Detect Second floor, room 253, classroom faucet 107 9/4/24 ND Non-Detect Second floor, room 254, drinking fountain 108 9/4/24 ND Non-Detect Second floor, room 254, classroom faucet 109 9/4/24 ND Non-Detect Second floor, Boys restroom, bathroom faucet, left, out of room 254 110 9/4/24 ND Non-Detect Second floor, Girls restroom, bathroom faucet, right, out of room 254 113 9/4/24 0.348 Low Second floor, staff restroom 260B, bathroom faucet 114 9/4/24 0.321 Low Second floor, room 261, drinking fountain 115 9/4/24 ND Non-Detect Second floor, room 261, classroom faucet 116 9/4/24 ND Non-Detect Second floor, room 262, drinking fountain 117 9/4/24 0.276 Low Second floor, room 262, classroom faucet 118 9/4/24 ND Non-Detect Second floor, room 260, classroom faucet 119 9/4/24 0.297 Low Second floor, room 260, water bottle filler 120 9/4/24 ND Non-Detect Second floor, room 263, drinking fountain 121 9/4/24 ND Non-Detect Second floor, room 263, classroom faucet 122 9/4/24 ND Non-Detect Second floor, room 264, drinking fountain 123 9/4/24 0.649 Low Second floor, room 264, classroom faucet 124 9/4/24 ND Non-Detect Second floor, Boys restroom, bathroom faucet, right, out of room 264 126 9/4/24 0.223 Low Second floor, Girls restroom, bathroom faucet, left, out of room 264 127 9/4/24 ND Non-Detect Second floor, Girls restroom, bathroom faucet, right, out of room 264 128 9/4/24 0.314 Low Second floor, library office, staff faucet 129 9/4/24 0.322 Low Fixtures Not Sampled
Fixtures listed above as “Not Tested” could not be sampled by PBS, as they were either shut off or inaccessible. PBS assigned them a number in sequence so they can be sampled later if they are brought back online.
-
On October 8, 2024, PBS Engineering and Environmental Inc. (PBS) performed drinking water sampling and analysis for lead at Wilkes Elementary School in Portland, Oregon. The testing was requested by Reynolds School District to meet requirements from the Oregon Department of Education (ODE) and Oregon Health Authority (OHA) to conduct testing for lead in school drinking water systems.
Lead in Water Test Notes
- The lead in water Action Level is 15 parts per billion (ppb).
- Any fixture testing at or above the action level of 15 ppb is immediately removed from service and cannot be returned to service until it has been remediated and passed follow-up testing.
- A "ND" or "non-detect" test result indicates no lead.
- Test results equal to or greater than the Action Level of 15 ppb are highlighted in red and precede a "Action Required" value.
- Test results near the Action Level of 15 ppb (12 to 14.99 ppb) are highlighted in orange and precede a "High" value.
Test Results
Fixture Location Description Fixture ID # Initial
Test DateInitial Test Result (ppb) Initial
LevelKitchen, North hand wash sink faucet 001 10/8/24 1.2 Low Kitchen, North food pre sink faucet, left 002 10/8/24 0.65 Low Kitchen, North food pre sink faucet, right 003 10/8/24 10.70 Moderate Kitchen, Central hand wash sink faucet 004 10/8/24 1.4 Low Kitchen, Central food pre sink faucet 005 10/8/24 0.49 Low Staff restroom 129, bathroom faucet 006 10/8/24 0.69 Low Cafeteria, West hand wash sink faucet 007 10/8/24 0.784 Low Room 126 music, drinking fountain 008 10/8/24 0.7 Low Room 126 music, classroom faucet 009 10/8/24 ND Non-Detect Cafeteria, boys restroom 123, bathroom faucet, left 010 10/8/24 0.863 Low Cafeteria, boys restroom 123, bathroom faucet, right 011 10/8/24 0.75 Low Cafeteria, girls restroom122, bathroom faucet, left 012 10/8/24 0.84 Low Cafeteria, girls restroom 122, bathroom faucet, right 013 10/8/24 1.10 Low Gym, water bottle filler 014 10/8/24 ND Non-Detect Gym, Staff restroom 120D, bathroom faucet 015 10/8/24 2.48 Low Nurse office 101, Nurse faucet 016 10/8/24 ND Non-Detect Nurse office 101, restroom, bathroom faucet 017 10/8/24 0.287 Low Staff lounge 107, south sink, staff faucet 018 10/8/24 0.21 Low Staff lounge 107, north sink, staff faucet 019 10/8/24 ND Non-Detect Staff room 105, staff faucet 020 10/8/24 3.95 Low Staff restroom 104, bathroom faucet 021 10/8/24 ND Non-Detect Restroom across from cafeteria, bathroom faucet 022 10/8/24 ND Non-Detect Room 114, north sink, classroom faucet, left 023 10/8/24 Not Tested - Room 114, north sink, classroom faucet, right 024 10/8/24 Not Tested - Room 114, west sink, classroom faucet 025 10/8/24 0.59 Low Room 141, left sink, drinking fountain 026 10/8/24 0.28 Low Room 141, left sink, classroom faucet 027 10/8/24 0.45 Low Room 141, right sink, drinking fountain 028 10/8/24 0.506 Low Room 141, right sink, classroom faucet 029 10/8/24 0.687 Low Restroom 141A, bathroom faucet 030 10/8/24 0.778 Low Restroom 141B, bathroom faucet (Not used for four years) 031 10/8/24 1.620 Low Room 142, left sink, drinking fountain 032 10/8/24 0.25 Low Room 142, left sink, classroom faucet 033 10/8/24 0.44 Low Room 142, right sink, drinking fountain 034 10/8/24 0.322 Low Room 142, right sink, classroom faucet 035 10/8/24 0.63 Low Restroom 142A, bathroom faucet 036 10/8/24 0.26 Low Room 140, drinking fountain 037 10/8/24 0.22 Low Room 140, classroom faucet 038 10/8/24 0.30 Low Room 140, water bottle filler 039 10/8/24 ND Non-Detect Room 143, left sink, drinking fountain 040 10/8/24 0.33 Low Room 143, left sink, classroom faucet 041 10/8/24 0.48 Low Room 143, right sink, drinking fountain 042 10/8/24 0.42 Low Room 143, right sink, classroom faucet 043 10/8/24 0.71 Low Restroom 143A, bathroom faucet 044 10/8/24 0.30 Low Room 144, left sink, drinking fountain 045 10/8/24 ND Non-Detect Room 144, left sink, classroom faucet 046 10/8/24 0.54 Low Room 144, right sink, drinking fountain 047 10/8/24 0.466 Low Room 144, right sink, classroom faucet 048 10/8/24 0.251 Low Restroom 144A, bathroom faucet 049 10/8/24 0.33 Low Restroom 140A, bathroom faucet 050 10/8/24 0.33 Low Restroom 150A, bathroom faucet 051 10/8/24 0.23 Low Room 151, drinking fountain 052 10/8/24 3.47 Low Room 151, classroom faucet 053 10/8/24 ND Non-Detect Room 152, drinking fountain 054 10/8/24 0.61 Low Room 152, classroom faucet 055 10/8/24 0.456 Low Room 150, classroom sink, classroom faucet 056 10/8/24 0.24 Low Room 150, water bottle filler 057 10/8/24 ND Non-Detect Room 153, drinking fountain 058 10/8/24 0.832 Low Room 153, classroom faucet 059 10/8/24 0.245 Low Room 154, drinking fountain 060 10/8/24 0.83 Low Room 154, classroom faucet 061 10/8/24 0.292 Low Boys restroom 155, bathroom faucet, left 062 10/8/24 0.819 Low Boys restroom 155, bathroom faucet, right 063 10/8/24 1.570 Low Girls restroom 156, bathroom faucet, left 064 10/8/24 1.29 Low Girls restroom 156, bathroom faucet, right 065 10/8/24 1.51 Low Restroom 160B, bathroom faucet 066 10/8/24 0.239 Low Room 161, drinking fountain 067 10/8/24 2.03 Low Room 161, classroom faucet 068 10/8/24 0.417 Low Room 162, drinking fountain 069 10/8/24 0.6 Low Room 162, classroom faucet 070 10/8/24 0.994 Low Room 160, classroom sink, classroom faucet 071 10/8/24 0.492 Low Room 160, water bottle filler 072 10/8/24 ND Non-Detect Room 163, drinking fountain 073 10/8/24 0.61 Low Room 163, classroom faucet 074 10/8/24 0.42 Low Room 164, drinking fountain 075 10/8/24 0.44 Low Room 164, classroom faucet 076 10/8/24 0.21 Low Boys restroom 165, bathroom faucet, left 077 10/8/24 1.330 Low Boys restroom 165, bathroom faucet, right 078 10/8/24 1.950 Low Girls restroom 166, bathroom faucet, left 079 10/8/24 1.23 Low Girls restroom 166, bathroom faucet, right 080 10/8/24 1.44 Low Second floor, Boys restroom 245, bathroom faucet, left 081 10/8/24 0.45 Low Second floor, Boys restroom 245, bathroom faucet, right 082 10/8/24 0.553 Low Second floor, Girls restroom 246, bathroom faucet, left 083 10/8/24 1.05 Low Second floor, Girls restroom 246, bathroom faucet, right 084 10/8/24 0.698 Low Second floor, room 244, drinking fountain 085 10/8/24 0.545 Low Second floor, room 244, classroom faucet 086 10/8/24 0.278 Low Second floor, Room 240, water bottle filler 087 10/8/24 ND Non-Detect Second floor, room 243, drinking fountain 088 10/8/24 0.495 Low Second floor, room 243, classroom faucet 089 10/8/24 0.298 Low Second floor, Room 240, classroom faucet 090 10/8/24 1.1 Low Second floor, room 242, drinking fountain 091 10/8/24 0.386 Low Second floor, room 242, classroom faucet 092 10/8/24 0.317 Low Second floor, Room 241, left sink, drinking fountain 093 10/8/24 1.86 Low Second floor, Room 241, left sink, classroom faucet 094 10/8/24 0.34 Low Second floor, Room 241, right sink, drinking fountain 095 10/8/24 0.501 Low Second floor, Room 241, right sink, classroom faucet 096 10/8/24 0.408 Low Second floor, restroom 241A, bathroom faucet 097 10/8/24 0.636 Low Second floor, restroom 240B, bathroom faucet 098 10/8/24 0.319 Low Second floor, library office 200A, staff faucet 099 10/8/24 0.598 Low Second floor, restroom 250B, bathroom faucet 100 10/8/24 0.285 Low Second floor, room 252, drinking fountain 101 10/8/24 ND Non-Detect Second floor, room 252, classroom faucet 102 10/8/24 1.16 Low Second floor, room 250, classroom faucet 103 10/8/24 ND Non-Detect Second floor, room 250, water bottle filler 104 10/8/24 ND Non-Detect Second floor, room 253, drinking fountain 105 10/8/24 1.8 Low Second floor, room 253, classroom faucet 106 10/8/24 1.42 Low Second floor, room 254, classroom faucet 107 10/8/24 0.767 Low Second floor, room 254, drinking fountain 108 10/8/24 0.568 Low Second floor, Boys restroom 255, bathroom faucet, left 109 10/8/24 0.89 Low Second floor, Boys restroom 255, bathroom faucet, right 110 10/8/24 0.863 Low Second floor, Girls restroom 256, bathroom faucet, left 111 10/8/24 0.951 Low Second floor, Girls restroom 256, bathroom faucet, right 112 10/8/24 0.407 Low Second floor, Restroom 260, bathroom faucet 113 10/8/24 0.269 Low Second floor, room 261, drinking fountain 114 10/8/24 1.5 Low Second floor, room 261, classroom faucet 115 10/8/24 0.336 Low Second floor, room 262, drinking fountain 116 10/8/24 0.355 Low Second floor, room 262, classroom faucet 117 10/8/24 1.33 Low Second floor, room 260, classroom faucet 118 10/8/24 1.64 Low Second floor, room 260, water bottle filler 119 10/8/24 ND Non-Detect Second floor, room 263, drinking fountain 120 10/8/24 1.73 Low Second floor, room 263, classroom faucet 121 10/8/24 1.95 Low Second floor, room 264, drinking fountain 122 10/8/24 2.07 Low Second floor, room 264, classroom faucet 123 10/8/24 0.269 Low Second floor, Boys restroom 265, bathroom faucet, left 124 10/8/24 1.55 Low Second floor, Boys restroom 265, bathroom faucet, right 125 10/8/24 0.483 Low Second floor, Girls restroom 266, bathroom faucet, left 126 10/8/24 0.719 Low Second floor, Girls restroom 266, bathroom faucet, right 127 10/8/24 0.757 Low Fixtures Not Sampled
The fixtures listed above with “Not Tested” could not be sampled by PBS, as they were either shut off or inaccessible. PBS assigned them a number in sequence so they can be sampled later if they are brought back online.
-
On September 27, 2024, PBS Engineering and Environmental Inc. (PBS) performed drinking water sampling and analysis for lead at Woodland Elementary School in Portland, Oregon. The testing was requested by Reynolds School District to meet requirements from the Oregon Department of Education (ODE) and Oregon Health Authority (OHA) to conduct testing for lead in school drinking water systems.
??On December 27, 2024, PBS Engineering and Environmental Inc. (PBS) performed drinking water re-sampling and analysis for lead at Woodland Elementary School in Fairview, Oregon. The test was requested by Reynolds School District and focus on elevated fixtures from last results, to meet requirements from the Oregon Department of Education (ODE) and Oregon Health Authority (OHA) to conduct testing for lead in school drinking water systems.
Lead in Water Test Notes
- The lead in water Action Level is 15 parts per billion (ppb).
- Any fixture testing at or above the action level of 15 ppb is immediately removed from service and cannot be returned to service until it has been remediated and passed follow-up testing.
- A "ND" or "non-detect" test result indicates no lead.
- Test results equal to or greater than the Action Level of 15 ppb are highlighted in red and precede a "Action Required" value.
- Test results near the Action Level of 15 ppb (12 to 14.99 ppb) are highlighted in orange and precede a "High" value.
Test Results
Fixture Location Description Fixture ID # Initial
Test DateInitial Test Result (ppb) Initial
LevelFinal
Retest DateFinal Test Result (ppb) Final
LevelKitchen, West hand wash sink faucet, left 001 9/27/24 13.3 High Kitchen, West hand wash sink faucet, right 002 9/27/24 1.21 Low Kitchen, Middle counter, food prep sink faucet 003 9/27/24 1.53 Low Kitchen, Hot pot faucet 004 9/27/24 67.4 Action Req. 12/26/24 1.3 Low Kitchen, East wall, food prep sink faucet, right 005 9/27/24 2.30 Low Kitchen, East wall, food prep sink faucet, left 006 9/27/24 3.92 Low Kitchen, Northeast wall, food prep sink faucet, right 007 9/27/24 0.219 Low Kitchen, East wall, food prep sink faucet, left (food waste system) 008 9/27/24 61.3 Action Req. 12/26/24 0.3 Low Kitchen, Staff restroom faucet 009 9/27/24 1.07 Low Gym, out of boys restroom, water bottle filler 010 9/27/24 0.216 Low Gym, Boys restroom faucet, left 011 9/27/24 2.12 Low Gym, Boys restroom faucet, right 012 9/27/24 1.64 Low Gym, Girls restroom faucet, left 013 9/27/24 2.18 Low Gym, Girls restroom faucet, right 014 9/27/24 1.33 Low Cafeteria, out of storage room, water bottle filler 015 9/27/24 ND Non-Detect Nurse office, nurse sink faucet 016 9/27/24 0.795 Low Teacher lounge, drinking water fountain 017 9/27/24 0.261 Low Teacher lounge, Men staff restroom faucet 018 9/27/24 3.04 Low Teacher lounge, Women staff restroom faucet (during renovation work) * 019 9/27/24 3.80 Low Hallway out of classroom 107, water bottle filler 020 9/27/24 ND Non-Detect Hallway out of elevator, water bottle filler 021 9/27/24 ND Non-Detect Boys restroom, next to elevator, left sink faucet, left 022 9/27/24 1.46 Low Boys restroom, next to elevator, left sink faucet, center 023 9/27/24 1.18 Low Boys restroom, next to elevator, left sink faucet, right 024 9/27/24 1.36 Low Boys restroom, next to elevator, right sink faucet, left 025 9/27/24 Not Tested - Boys restroom, next to elevator, right sink faucet, center 026 9/27/24 Not Tested - Boys restroom, next to elevator, right sink faucet, right 027 9/27/24 Not Tested - Hallway out of classroom 103, water bottle filler 028 9/27/24 ND Non-Detect Hallway out of classroom 115 (SPED room), water bottle filler 029 9/27/24 ND Non-Detect Classroom 115 (SPED room), restroom sink faucet 030 9/27/24 0.752 Low Classroom ART/CRAFT 031 9/27/24 Not Tested - Classroom 107, restroom sink faucet 032 9/27/24 4.05 Low Second floor, out of elevator, water bottle filler 033 9/27/24 ND Non-Detect Second floor, staff restroom faucet 034 9/27/24 ND Non-Detect Second floor, boys restroom faucet, left sink, left 035 9/27/24 6.85 Low Second floor, boys restroom faucet, left sink, center 036 9/27/24 2.44 Low Second floor, boys restroom faucet, left sink, right 037 9/27/24 3.96 Low Second floor, boys restroom faucet, right sink, left 038 9/27/24 Not Tested - Second floor, boys restroom faucet, right sink, center 039 9/27/24 Not Tested - Second floor, boys restroom faucet, right sink, right 040 9/27/24 Not Tested - Second floor, girls restroom faucet, left sink, left 041 9/27/24 Not Tested - Second floor, girls restroom faucet, left sink, center 042 9/27/24 4.56 Low Second floor, girls restroom faucet, left sink, right 043 9/27/24 4.63 Low Second floor, girls restroom faucet, right sink, left 044 9/27/24 3.58 Low Second floor, girls restroom faucet, right sink, center 045 9/27/24 3.87 Low Second floor, girls restroom faucet, right sink, right 046 9/27/24 3.99 Low Second floor, hallway out of east ELD classroom, water bottle filler 047 9/27/24 ND Non-Detect Second floor, East ELD classroom, restroom faucet 048 9/27/24 0.770 Low Girls restroom, next to elevator, left sink faucet, left 049 9/27/24 5.12 Low Girls restroom, next to elevator, left sink faucet, center 050 9/27/24 3.34 Low Girls restroom, next to elevator, left sink faucet, right 051 9/27/24 3.68 Low Girls restroom, next to elevator, right sink faucet, left 052 9/27/24 4.04 Low Girls restroom, next to elevator, right sink faucet, center 053 9/27/24 2.74 Low Girls restroom, next to elevator, right sink faucet, right 054 9/27/24 3.19 Low Staff restroom, next to elevator, restroom sink faucet 055 9/27/24 ND Non-Detect Outside spigot, West exterior wall, covered playground 056 9/27/24 1.64 Low Classroom 101, classroom faucet 057 9/27/24 3.07 Low Classroom 102, classroom faucet 058 9/27/24 0.381 Low Classroom 103, classroom faucet 059 9/27/24 0.330 Low Classroom 104, classroom faucet 060 9/27/24 2.89 Low Classroom 105, classroom faucet 061 9/27/24 0.401 Low Classroom 106, classroom faucet 062 9/27/24 0.676 Low Classroom 115, classroom faucet 063 9/27/24 0.388 Low Classroom 114, classroom faucet 064 9/27/24 9.29 Moderate Classroom 113, classroom faucet 065 9/27/24 1.05 Low Classroom 112, classroom faucet 066 9/27/24 0.236 Low Classroom 111, classroom faucet 067 9/27/24 2.90 Low Classroom 110, classroom faucet 068 9/27/24 ND Non-Detect Classroom 109, classroom faucet 069 9/27/24 14.7 High Classroom 108, classroom faucet 070 9/27/24 0.972 Low Teacher Lounge, staff faucet 071 9/27/24 ND Non-Detect Resource room, staff faucet 072 9/27/24 1.81 Low Classroom 207, classroom faucet 073 9/27/24 7.56 Low Classroom 208, classroom faucet 074 9/27/24 1.46 Low Classroom 209, classroom faucet 075 9/27/24 1.02 Low Classroom 210, classroom faucet 076 9/27/24 8.87 Moderate Classroom 211, classroom faucet 077 9/27/24 0.543 Low Classroom 212, classroom faucet 078 9/27/24 0.214 Low Classroom 213, classroom faucet 079 9/27/24 2.43 Low Classroom 214, classroom faucet 080 9/27/24 1.58 Low Classroom 215, classroom faucet 081 9/27/24 1.17 Low Fixtures Not Sampled
The fixtures labeled “Not Tested” above could not be sampled by PBS, as they were either shut off or inaccessible. PBS assigned them a number in sequence so they can be sampled later if they are brought back online.
-
On September 17, 2024, PBS Engineering and Environmental Inc. (PBS) performed drinking water sampling and analysis for lead at H.B. Lee Middle School in Portland, Oregon. The testing was requested by Reynolds School District to meet requirements from the Oregon Department of Education (ODE) and Oregon Health Authority (OHA) to conduct testing for lead in school drinking water systems.
Lead in Water Test Notes
- The lead in water Action Level is 15 parts per billion (ppb).
- Any fixture testing at or above the action level of 15 ppb is immediately removed from service and cannot be returned to service until it has been remediated and passed follow-up testing.
- A "ND" or "non-detect" test result indicates no lead.
- Test results equal to or greater than the Action Level of 15 ppb are highlighted in red and precede a "Action Required" value.
- Test results near the Action Level of 15 ppb (12 to 14.99 ppb) are highlighted in orange and precede a "High" value.
Test Results
Fixture Location Description Fixture ID # Initial
Test DateInitial Test Result (ppb) Initial
LevelFinal
Retest DateFinal Test Result (ppb) Final
LevelKitchen, hand wash sink faucet 001 9/17/24 0.776 Low Kitchen, east, food prep sink faucet 002 9/17/24 1.06 Low Kitchen, northeast, food prep sink faucet 003 9/17/24 ND Non-Detect Kitchen, south, food prep sink faucet 004 9/17/24 2.16 Low Cafeteria, water bottle filler 005 9/17/24 ND Non-Detect Classroom 609, drinking fountain 006 9/17/24 36.7 Action Req. 12/12/24 16.7 Action Req. Classroom 610, drinking fountain 007 9/17/24 23.0 Action Req. 12/12/24 20.2 Action Req. Classroom 608, drinking fountain 008 9/17/24 5.27 Moderate Classroom 607, drinking fountain 009 9/17/24 11.1 Action Req. Girls west restroom, bathroom faucet 010 9/17/24 3.39 Low Boys west restroom, bathroom faucet 011 9/17/24 2.55 Low Classroom 606, classroom faucet 012 9/17/24 6.59 Moderate Classroom 606, classroom faucet 013 9/17/24 7.16 Moderate Classroom 606, classroom faucet 014 9/17/24 1.53 Low Classroom 606, classroom faucet 015 9/17/24 0.936 Low Classroom 606, classroom faucet 016 9/17/24 0.753 Low Classroom 606, classroom faucet 017 9/17/24 0.773 Low Classroom 606, classroom faucet 018 9/17/24 0.342 Low Classroom 606, classroom faucet 019 9/17/24 1.20 Low Hallway out of classroom 605, water bottle filler 020 9/17/24 ND Non-Detect Hallway out of classroom 301, water bottle filler 021 9/17/24 0.358 Low Hallway out of classroom 501, water bottle filler 022 9/17/24 ND Non-Detect Classroom 406, classroom faucet 023 9/17/24 3.69 Low Classroom 407 024 9/17/24 Not Tested - Hallway out of classroom 306, water bottle filler 025 9/17/24 ND Non-Detect Girls locker room, water bottle filler 026 9/17/24 ND Non-Detect Girls locker room, left faucet 027 9/17/24 6.69 Moderate Girls locker room, right faucet 028 9/17/24 Not Tested - Boys locker room, water bottle filler 029 9/17/24 ND Non-Detect Boys locker room, bathroom faucet 030 9/17/24 6.67 Moderate Boys locker room, right faucet 031 9/17/24 Not Tested - Girls east restroom, bathroom faucet 032 9/17/24 0.356 Low Boys east restroom, bathroom faucet, left 033 9/17/24 1.04 Low Hallway out of classroom 206, water bottle filler 034 9/17/24 ND Non-Detect Women staff restroom, bathroom faucet 035 9/17/24 1.35 Low Men staff restroom, bathroom faucet 036 9/17/24 3.78 Low Hallway out of classroom 201, water bottle filler 037 9/17/24 ND Non-Detect Main office, staff restroom, bathroom faucet 038 9/17/24 2.07 Low Boys restroom across library, left faucet 039 9/17/24 0.627 Low Boys restroom across library, right faucet 040 9/17/24 Not Tested - Girls restroom across library 041 9/17/24 0.483 Low Multi-purpose room, Girls restroom, 042 9/17/24 9.98 High Multi-purpose room, Boys restroom, 043 9/17/24 4.53 Low Multi-purpose room, water bottle filler 044 9/17/24 ND Non-Detect Classroom 104, classroom faucet 045 9/17/24 18.8 Action Req. 12/12/2024 0.41 Low Teacher lounge, drinking fountain 046 9/17/24 ND Non-Detect Teacher lounge, staff faucet 047 9/17/24 0.479 Low Classroom 306, classroom faucet 048 9/17/24 4.04 Low Classroom 406, North sink, classroom faucet 049 9/17/24 1.34 Low Classroom 406, South sink, classroom faucet 050 9/17/24 2.20 Low Nurse office, nurse sink faucet 051 9/17/24 1.73 Low Main office, work room, staff faucet 052 9/17/24 2.13 Low Fixtures Not Sampled
The fixtures listed as “Not Tested” above could not be sampled by PBS, as they were either shut off or inaccessible. PBS assigned them a number in sequence so they can be sampled later if they are brought back online.
-
On September 24, 2024, PBS Engineering and Environmental Inc. (PBS) performed drinking water sampling and analysis for lead at Reynolds Middle School in Portland, Oregon. The testing was requested by Reynolds School District to meet requirements from the Oregon Department of Education (ODE) and Oregon Health Authority (OHA) to conduct testing for lead in school drinking water systems.
Lead in Water Test Notes
- The lead in water Action Level is 15 parts per billion (ppb).
- Any fixture testing at or above the action level of 15 ppb is immediately removed from service and cannot be returned to service until it has been remediated and passed follow-up testing.
- A "ND" or "non-detect" test result indicates no lead.
- Test results equal to or greater than the Action Level of 15 ppb are highlighted in red and precede a "Action Required" value.
- Test results near the Action Level of 15 ppb (12 to 14.99 ppb) are highlighted in orange and precede a "High" value.
Test Results
Fixture Location Description Fixture ID # Initial
Test DateInitial Test Result (ppb) Initial
LevelFinal
Retest DateFinal Test Result (ppb) Final
LevelHallway out of main office 001 9/24/24 ND Non-Detect Girls restroom out of main office, bathroom faucet, left 002 9/24/24 2.32 Low Girls restroom out of main office, bathroom faucet, right 003 9/24/24 2.24 Low Boys restroom out of main office, bathroom faucet, left 004 9/24/24 3.94 Low Boys restroom out of main office, right 005 9/24/24 Not Tested - Girls restroom out of classroom 401, bathroom faucet, left 006 9/24/24 3.46 Low Girls restroom out of classroom 401, bathroom faucet, right 007 9/24/24 4.07 Low Hallway out of classroom 403 008 9/24/24 Not Tested - Boys restroom out of classroom 401, bathroom faucet, left 009 9/24/24 4.37 Low Boys restroom out of classroom 401, bathroom faucet, left center 010 9/24/24 2.08 Low Boys restroom out of classroom 401, bathroom faucet, right center 011 9/24/24 4.45 Low Boys restroom out of classroom 401, bathroom faucet, right 012 9/24/24 11.5 Moderate Classroom 407, classroom faucet 013 9/24/24 3.82 Low Classroom 613, bathroom faucet 014 9/24/24 9.21 Moderate Hallway out of main gym, south entrance, water bottle filler 015 9/24/24 ND Non-Detect Men staff restroom out of main gym, bathroom faucet, left 016 9/24/24 5.33 Low Men staff restroom out of main gym, bathroom faucet, center 017 9/24/24 5.21 Low Men staff restroom out of main gym, bathroom faucet, right 018 9/24/24 7.06 Low Women staff restroom out of main gym, bathroom faucet, left 019 9/24/24 3.79 Low Women staff restroom out of main gym, bathroom faucet, center 020 9/24/24 1.15 Low Women staff restroom out of main gym, bathroom faucet, right 021 9/24/24 12.9 High Boys locker room, east restroom faucet, left 022 9/24/24 2.40 Low Boys locker room, east restroom faucet, right 023 9/24/24 2.20 Low Boys locker room, west restroom faucet, left 024 9/24/24 4.54 Low Boys locker room, west restroom faucet, right 025 9/24/24 6.29 Low Boys locker room, out of coach room, water bottle filler 026 9/24/24 ND Non-Detect Kitchen, west hand wash sink faucet 027 9/24/24 2.75 Low Kitchen, east food prep sink faucet 028 9/24/24 8.48 Moderate Kitchen, south wall food prep sink faucet, left 029 9/24/24 40.4 Action Req. 12/27/2024 1.21 Low Kitchen, south wall food prep sprayer, center 030 9/24/24 0.451 Low Kitchen, south wall food prep sink faucet, right 031 9/24/24 0.670 Low Kitchen, southwest food prep sink faucet 032 9/24/24 2.22 Low Kitchen, bathroom faucet 033 9/24/24 2.91 Low Main office, northwest bathroom faucet 034 9/24/24 5.61 Low Main office, north bathroom faucet 035 9/24/24 3.66 Low Nurse office, boys restroom faucet 036 9/24/24 7.24 Low Nurse office, girls restroom faucet 037 9/24/24 12.8 High Next to classroom 323, boys restroom faucet, left 038 9/24/24 5.17 Low Next to classroom 323, boys restroom faucet, left center 039 9/24/24 5.21 Low Next to classroom 323, boys restroom faucet, right center 040 9/24/24 3.88 Low Next to classroom 323, boys restroom faucet, right 041 9/24/24 5.32 Low Hallway out of classroom 323, water bottle filler 042 9/24/24 0.505 Low Next to classroom 323, girls restroom faucet, left 043 9/24/24 1.92 Low Next to classroom 323, girls restroom faucet, right 044 9/24/24 2.55 Low Northwest hall, women staff bathroom faucet, left 045 9/24/24 5.41 Low Northwest hall, women staff bathroom faucet, left center 046 9/24/24 3.30 Low Northwest hall, women staff bathroom faucet, right center 047 9/24/24 3.82 Low Northwest hall, women staff bathroom faucet, right 048 9/24/24 3.34 Low Northwest hall, water bottle filler out of women staff bathroom (Near classroom 803) 049 9/24/24 ND Non-Detect Northwest hall, men staff bathroom faucet, left 050 9/24/24 3.26 Low Northwest hall, men staff bathroom faucet, left center 051 9/24/24 2.46 Low Northwest hall, men staff bathroom faucet, right center 052 9/24/24 3.00 Low Northwest hall, men staff bathroom faucet, right 053 9/24/24 1.77 Low Northwest hall, water bottle filler out of boys bathroom 054 9/24/24 ND Non-Detect Northwest hall, boys bathroom faucet (Near classroom 503) 055 9/24/24 1.53 Low Northwest hall, water bottle filler out of girls bathroom 056 9/24/24 ND Non-Detect Northwest hall, girls bathroom faucet (Near classroom 503) 057 9/24/24 0.309 Low Girls locker room, north restroom faucet, left 058 9/24/24 3.54 Low Girls locker room, north restroom faucet, left center 059 9/24/24 5.61 Low Girls locker room, north restroom faucet, right center 060 9/24/24 13.7 High Girls locker room, north restroom faucet, right 061 9/24/24 6.17 Low Girls locker room, east wall, water bottle filler 062 9/24/24 0.339 Low Hallway out of theater, water bottle filler 063 9/24/24 0.447 Low Girls restroom out of north gym, left 064 9/24/24 11.9 Moderate Girls restroom out of north gym, right 065 9/24/24 5.51 Low Boys restroom out of north gym 066 9/24/24 4.33 Low East building, bathroom faucet out of room 901 067 9/24/24 1.06 Low East building, water bottle filler out of room 901 068 9/24/24 ND Non-Detect East building, water bottle filler out of room 900 069 9/24/24 0.975 Low East building, bathroom faucet out of room 900 070 9/24/24 13.1 High Swimming pool, girls locker room 071 9/24/24 Not Tested - Swimming pool, girls locker room, hand wash sink faucet 072 9/24/24 0.895 Low Swimming pool, boys locker room, drinking water fountain 073 9/24/24 7.65 Low Swimming pool, boys locker room, hand wash sink faucet 074 9/24/24 7.50 Low Outside spigot, east exterior wall outside of classroom 603 075 9/24/24 226 Action Req. Outside spigot, yard, west exterior wall outside of theater 076 9/24/24 62.2 Action Req. Art classroom, classroom faucet, left 077 9/24/24 1.34 Low Art classroom, classroom faucet, right 078 9/24/24 4.69 Low Classroom 409, classroom faucet 079 9/24/24 4.91 Low Classroom 411, classroom faucet 080 9/24/24 Not Tested - Classroom 612, drinking fountain 081 9/24/24 ND Non-Detect Classroom 612, classroom faucet 082 9/24/24 0.359 Low Classroom 613, classroom faucet 083 9/24/24 4.04 Low Teacher lounge, drinking fountain 084 9/24/24 0.325 Low Teacher lounge, staff faucet 085 9/24/24 4.31 Low Fixtures Not Sampled
The fixtures listed “Not Tested” above could not be sampled by PBS, as they were either shut off or inaccessible. PBS assigned them a number in sequence so they can be sampled later if they are brought back online.
-
On September 26, 2024, PBS Engineering and Environmental Inc. (PBS) performed drinking water sampling and analysis for lead at Walt Morey Middle School in Portland, Oregon. The testing was requested by Reynolds School District to meet requirements from the Oregon Department of Education (ODE) and Oregon Health Authority (OHA) to conduct testing for lead in school drinking water systems.
Lead in Water Test Notes
- The lead in water Action Level is 15 parts per billion (ppb).
- Any fixture testing at or above the action level of 15 ppb is immediately removed from service and cannot be returned to service until it has been remediated and passed follow-up testing.
- A "ND" or "non-detect" test result indicates no lead.
- Test results equal to or greater than the Action Level of 15 ppb are highlighted in red and precede a "Action Required" value.
- Test results near the Action Level of 15 ppb (12 to 14.99 ppb) are highlighted in orange and precede a "High" value.
Test Results
Fixture Location Description Fixture ID # Initial
Test DateInitial Test Result (ppb) Initial
LevelKitchen, Northwest hand wash sink faucet 001 9/26/24 1.38 Low Kitchen, West food prep sink faucet, left 002 9/26/24 2.29 Low Kitchen, West food prep sink faucet, right 003 9/26/24 1.19 Low Kitchen, East food prep sink faucet, 004 9/26/24 0.464 Low Kitchen, East food waste system sink faucet, right 005 9/26/24 55.3 Action Req. Kitchen, Southeast hand wash sink faucet, left 006 9/26/24 4.32 Low Kitchen, Southeast hand wash sink faucet, right 007 9/26/24 6.11 Low Kitchen, staff restroom faucet 008 9/26/24 1.52 Low Cafeteria, water bottle filler, out of kitchen 009 9/26/24 ND Non-Detect Game room, restroom faucet (Next to kitchen) 010 9/26/24 0.419 Low Out of boys restroom, water bottle filler (Next to main entrance) 011 9/26/24 ND Non-Detect Out of girls restroom, water bottle filler (Next to main entrance) 012 9/26/24 ND Non-Detect Boys restroom, restroom faucet, left (Next to main entrance) 013 9/26/24 2.34 Low Boys restroom, restroom faucet, left center (Next to main entrance) 014 9/26/24 0.738 Low Boys restroom, restroom faucet, right center (Next to main entrance) 015 9/26/24 Not Tested - Boys restroom, restroom faucet, right (Next to main entrance) 016 9/26/24 1.53 Low Girls restroom, restroom faucet, left (Next to main entrance) 017 9/26/24 3.52 Low Girls restroom, restroom faucet, left center (Next to main entrance) 018 9/26/24 1.13 Low Girls restroom, restroom faucet, right center (Next to main entrance) 019 9/26/24 1.08 Low Girls restroom, restroom faucet, right (Next to main entrance) 020 9/26/24 1.73 Low Nurse office, nurse sink faucet 021 9/26/24 0.280 Low Main office, restroom faucet 022 9/26/24 0.436 Low Staff work room, drinking water fountain 023 9/26/24 ND Non-Detect Teacher lounge room, restroom faucet 024 9/26/24 0.207 Low Room music 90, drinking water fountain 025 9/26/24 0.379 Low Faculty restroom, North Hall, restroom faucet 026 9/26/24 0.482 Low Girls restroom, restroom faucet, left (Next to POD 100) 027 9/26/24 8.64 Moderate Girls restroom, restroom faucet, center (Next to POD 100) 028 9/26/24 3.12 Low Girls restroom, restroom faucet, right (Next to POD 100) 029 9/26/24 4.33 Low Boys restroom, restroom faucet, left (Next to POD 110) 030 9/26/24 11.6 Moderate Boys restroom, restroom faucet, center (Next to POD 110) 031 9/26/24 4.15 Low Boys restroom, restroom faucet, right (Next to POD 110) 032 9/26/24 4.03 Low Out of girls restroom, water bottle filler (Next to POD 100) 033 9/26/24 ND Non-Detect Out of boys restroom, water bottle filler (Next to POD 110) 034 9/26/24 ND Non-Detect Girls restroom, restroom faucet, left (Next to storage room 121A) 035 9/26/24 5.76 Low Girls restroom, restroom faucet, center (Next to storage room 121A) 036 9/26/24 2.52 Low Girls restroom, restroom faucet, right (Next to storage room 121A) 037 9/26/24 3.40 Low Library, restroom faucet 038 9/26/24 0.344 Low Portable building, main entrance, water bottle filler 039 9/26/24 ND Non-Detect Portable building, women restroom faucet, left 040 9/26/24 2.11 Low Portable building, women restroom faucet, right 041 9/26/24 1.57 Low Portable building, men restroom faucet, left 042 9/26/24 1.54 Low Portable building, men restroom faucet, right 043 9/26/24 1.49 Low 2nd floor, faculty restroom, north hall, restroom faucet 044 9/26/24 0.808 Low 2nd floor, boys restroom, restroom faucet, left (Next to POD 200) 045 9/26/24 2.83 Low 2nd floor, boys restroom, restroom faucet, center (Next to POD 200) 046 9/26/24 1.48 Low 2nd floor, boys restroom, restroom faucet, right (Next to POD 200) 047 9/26/24 2.24 Low 2nd floor, boys restroom, restroom faucet, left (Next to POD 210) 048 9/26/24 4.83 Low 2nd floor, boys restroom, restroom faucet, center (Next to POD 210) 049 9/26/24 1.30 Low 2nd floor, boys restroom, restroom faucet, right (Next to POD 210) 050 9/26/24 2.09 Low 2nd floor, out of girls restroom, water bottle filler (Next to POD 200) 051 9/26/24 ND Non-Detect 2nd floor, out of boys restroom, water bottle filler (Next to POD 210) 052 9/26/24 ND Non-Detect 2nd floor, girls restroom, restroom faucet, left (Next to POD 200) 053 9/26/24 3.31 Low 2nd floor, girls restroom, restroom faucet, center (Next to POD 200) 054 9/26/24 1.22 Low 2nd floor, girls restroom, restroom faucet, right (Next to POD 200) 055 9/26/24 3.11 Low Main gym, out of boys locker room, water bottle filler 056 9/26/24 ND Non-Detect Boys locker room, restroom faucet, left 057 9/26/24 2.86 Low Boys locker room, restroom faucet, left center 058 9/26/24 1.30 Low Boys locker room, restroom faucet, right center 059 9/26/24 1.13 Low Boys locker room, restroom faucet, right 060 9/26/24 1.88 Low Boys locker room, coach restroom faucet 061 9/26/24 0.704 Low Girls locker room, restroom faucet, left 062 9/26/24 Not Tested - Girls locker room, restroom faucet, left center 063 9/26/24 Not Tested - Girls locker room, restroom faucet, right center 064 9/26/24 2.22 Low Girls locker room, restroom faucet, right 065 9/26/24 Not Tested - Girls locker room, coach restroom faucet 066 9/26/24 23.8 Action Req. Game room, classroom faucet 067 9/26/24 1.92 Low Staff work room, staff faucet 068 9/26/24 0.377 Low Art classroom, classroom faucet 069 9/26/24 1.27 Low Music classroom, classroom faucet 070 9/26/24 ND Non-Detect Pod 100, classroom 101, classroom faucet 071 9/26/24 0.658 Low Pod 100, classroom 102, classroom faucet 072 9/26/24 1.45 Low Pod 100, activity area, classroom faucet 073 9/26/24 2.26 Low Pod 100, classroom 103, classroom faucet 074 9/26/24 1.77 Low Pod 120, activity area, classroom faucet 075 9/26/24 2.57 Low Library office, staff faucet 076 9/26/24 2.54 Low Pod 110, classroom 111, classroom faucet 077 9/26/24 0.642 Low Pod 110, classroom 112, classroom faucet 078 9/26/24 0.807 Low Pod 110, activity area, classroom faucet 079 9/26/24 2.06 Low Pod 110, classroom 113, classroom faucet 080 9/26/24 1.78 Low Pod 110, classroom 114, classroom faucet 081 9/26/24 1.14 Low Pod 200, classroom 201, classroom faucet 082 9/26/24 ND Non-Detect Pod 200, classroom 202, classroom faucet 083 9/26/24 1.37 Low Pod 200, activity area, classroom faucet 084 9/26/24 0.286 Low Pod 200, classroom 203, classroom faucet 085 9/26/24 0.542 Low Pod 200, classroom 204, classroom faucet 086 9/26/24 1.42 Low Pod 220, classroom 222, classroom faucet 087 9/26/24 1.80 Low Pod 220, classroom 223, classroom faucet 088 9/26/24 1.65 Low Pod 220, activity area, classroom faucet 089 9/26/24 0.235 Low Pod 220, classroom 224, classroom faucet 090 9/26/24 2.25 Low Pod 210, classroom 211, classroom faucet 091 9/26/24 0.791 Low Pod 210, classroom 212, classroom faucet 092 9/26/24 1.72 Low Pod 210, activity area, classroom faucet 093 9/26/24 1.34 Low Pod 210, classroom 213, classroom faucet 094 9/26/24 0.980 Low Pod 210, classroom 214, classroom faucet 095 9/26/24 0.331 Low Fixtures Not Sampled
The fixtures listed “Not Tested” above could not be sampled by PBS, as they were either shut off or inaccessible. PBS assigned them a number in sequence so they can be sampled later if they are brought back online.
-
On September 18, 2024, PBS Engineering and Environmental Inc. (PBS) performed drinking water sampling and analysis for lead at Reynolds High School in Troutdale, Oregon. The testing was requested by Reynolds School District to meet requirements from the Oregon Department of Education (ODE) and Oregon Health Authority (OHA) to conduct testing for lead in school drinking water systems.
Lead in Water Test Notes
- The lead in water Action Level is 15 parts per billion (ppb).
- Any fixture testing at or above the action level of 15 ppb is immediately removed from service and cannot be returned to service until it has been remediated and passed follow-up testing.
- A "ND" or "non-detect" test result indicates no lead.
- Test results equal to or greater than the Action Level of 15 ppb are highlighted in red and precede a "Action Required" value.
- Test results near the Action Level of 15 ppb (12 to 14.99 ppb) are highlighted in orange and precede a "High" value.
Test Results
Fixture Location Description Fixture ID # Initial
Test DateInitial Test Result (ppb) Initial
LevelKitchen, East hand wash sink faucet 001 9/18/24 ND Non-Detect Kitchen, Northwest hand wash sink faucet 002 9/18/24 0.209 Low Kitchen, West food prep sink faucet (Food waste system) 003 9/18/24 ND Non-Detect Kitchen, West food prep sink faucet 004 9/18/24 ND Non-Detect Kitchen, West hand wash sink faucet 005 9/18/24 ND Non-Detect Kitchen, Southwest food prep sink faucet 006 9/18/24 0.239 Low Kitchen, Hot pot faucet 007 9/18/24 20.7 Action Req. Kitchen, Southwest hand wash sink faucet 008 9/18/24 ND Non-Detect Kitchen, South hand wash sink faucet 009 9/18/24 ND Non-Detect Kitchen, Sink faucet 010 9/18/24 0.306 Low Kitchen, Bathroom sink faucet 011 9/18/24 0.233 Low Classroom 405, classroom faucet, left 012 9/18/24 0.993 Low Classroom 405, classroom faucet, center 013 9/18/24 0.875 Low Classroom 405, classroom faucet, right 014 9/18/24 0.681 Low Classroom 407, classroom faucet, south 015 9/18/24 0.360 Low Classroom 407, classroom faucet, southwest 016 9/18/24 0.803 Low Classroom 407, classroom faucet, west 017 9/18/24 1.03 Low Classroom 407, classroom faucet, northwest 018 9/18/24 ND Non-Detect Classroom 409, classroom faucet, south 019 9/18/24 1.81 Low Classroom 409, classroom faucet, southwest 020 9/18/24 0.937 Low Classroom 409, classroom faucet, west 021 9/18/24 2.33 Low Classroom 409, classroom faucet, northwest 022 9/18/24 2.84 Low Classroom 411, classroom faucet (Leaking) 023 9/18/24 0.767 Low Restroom 413, bathroom faucet 024 9/18/24 0.361 Low Restroom 415, bathroom faucet 025 9/18/24 0.591 Low Classroom 402, bathroom faucet 026 9/18/24 1.06 Low Classroom 402, sink faucet 027 9/18/24 ND Non-Detect Classroom 402, sink faucet 028 9/18/24 0.582 Low Classroom 401, hand wash sink faucet, east 029 9/18/24 0.618 Low Classroom 401, food prep sink, left 030 9/18/24 0.760 Low Classroom 401, food prep sink, center left 031 9/18/24 1.88 Low Classroom 401, food prep sink, center right 032 9/18/24 0.835 Low Classroom 401, food prep sink, right 033 9/18/24 2.23 Low Classroom 401, food prep sink, south 034 9/18/24 0.813 Low Classroom 401, food prep sink, southeast 1 035 9/18/24 2.99 Low Classroom 401, food prep sink, southeast 2 036 9/18/24 4.05 Low Classroom 401, east food prep sink, left 037 9/18/24 0.400 Low Classroom 401, east food prep sink, right 038 9/18/24 0.309 Low Classroom 401, hand wash sink faucet, next to doorway 039 9/18/24 0.706 Low Hall out of Women Restroom 33, water bottle filler 040 9/18/24 ND Non-Detect Women Restroom 33, bathroom faucet, left 041 9/18/24 2.64 Low Women Restroom 33, bathroom faucet, right 042 9/18/24 1.94 Low Men Restroom 32, bathroom faucet, left 043 9/18/24 2.01 Low Men Restroom 32, bathroom faucet, right 044 9/18/24 1.61 Low Staff lounge 201, staff sink faucet 045 9/18/24 0.608 Low Men Restroom 208, bathroom faucet, left 046 9/18/24 0.654 Low Men Restroom 208, bathroom faucet, right 047 9/18/24 0.464 Low Classroom 219, classroom faucet 048 9/18/24 8.94 Moderate Hall out of classroom 219, water bottle filler 049 9/18/24 ND Non-Detect Men Restroom 218, bathroom faucet 050 9/18/24 2.22 Low Women Restroom 217, bathroom faucet 051 9/18/24 4.09 Low Classroom 216, classroom faucet 052 9/18/24 0.560 Low Hall out of classroom 109, water bottle filler 053 9/18/24 ND Non-Detect Restroom 117, bathroom faucet 054 9/18/24 0.868 Low Restroom 116, bathroom faucet 055 9/18/24 0.657 Low Women Restroom 120, bathroom faucet, left 056 9/18/24 1.23 Low Women Restroom 120, bathroom faucet, right 057 9/18/24 0.586 Low Men Restroom 121, bathroom faucet, left 058 9/18/24 1.10 Low Men Restroom 121, bathroom faucet, right 059 9/18/24 0.953 Low Hall out of classroom 121, water bottle filler 060 9/18/24 ND Non-Detect Classroom 125, water bottle filler 061 9/18/24 ND Non-Detect Classroom 125 restroom, bathroom faucet 062 9/18/24 2.90 Low Classroom 128, water bottle filler 063 9/18/24 ND Non-Detect Classroom 128 restroom, bathroom faucet 064 9/18/24 4.81 Low Restroom 108, bathroom faucet 065 9/18/24 0.573 Low Restroom 107, bathroom faucet 066 9/18/24 0.472 Low Women Restroom 104, bathroom faucet, left 067 9/18/24 0.934 Low Women Restroom 104, bathroom faucet, right 068 9/18/24 0.454 Low West entrance, water bottle filler 069 9/18/24 ND Non-Detect Men Restroom 53, bathroom faucet, left 070 9/18/24 1.66 Low Men Restroom 53, bathroom faucet, center 071 9/18/24 1.30 Low Men Restroom 53, bathroom faucet, right 072 9/18/24 5.12 Low Women Restroom 51, bathroom faucet, left 073 9/18/24 2.33 Low Women Restroom 51, bathroom faucet, center 074 9/18/24 4.27 Low Women Restroom 51, bathroom faucet, right 075 9/18/24 2.45 Low Health center, Toilet 104, bathroom faucet 076 9/18/24 0.450 Low Health center, Dental 105, nurse sink faucet 077 9/18/24 0.318 Low Health center, ADA Exam 106, nurse sink faucet 078 9/18/24 0.447 Low Health center, 107 Exam, nurse sink faucet 079 9/18/24 0.219 Low Health center, Room 113, staff sink faucet 080 9/18/24 0.328 Low Health center, 108 Exam, nurse sink faucet 081 9/18/24 0.214 Low Health center, Toilet 109, bathroom faucet 082 9/18/24 0.329 Low Health center, Medical Supply Room, right sink 083 9/18/24 0.312 Low Health center, Medical Supply Room, left sink 084 9/18/24 2.89 Low Men Restroom 511, bathroom faucet 085 9/18/24 1.37 Low Hall out of classroom 517, water bottle filler 086 9/18/24 ND Non-Detect Women Restroom 512, bathroom faucet 087 9/18/24 1.62 Low Hall out of classroom 614, water bottle filler 088 9/18/24 ND Non-Detect Hall out of storage 622, water bottle filler 089 9/18/24 ND Non-Detect Library, Room 630B, staff sink 090 9/18/24 6.67 Low Women Restroom 712, bathroom faucet 091 9/18/24 1.44 Low Hall out of classroom 717, water bottle filler 092 9/18/24 ND Non-Detect Men Restroom 711, bathroom faucet 093 9/18/24 2.16 Low Restroom 63, bathroom faucet 094 9/18/24 Not Tested - Restroom 62, bathroom faucet 095 9/18/24 0.844 Low Men restroom 61, bathroom faucet 096 9/18/24 0.635 Low Hall out of Men restroom 61, water bottle filler 097 9/18/24 ND Non-Detect Women restroom 60, bathroom faucet 098 9/18/24 1.01 Low Men restroom 58, bathroom faucet 099 9/18/24 0.970 Low Hall out of restroom 58, water bottle filler 100 9/18/24 ND Non-Detect Women restroom 57, bathroom faucet 101 9/18/24 1.88 Low Main office, Restroom27 102 9/18/24 ND Non-Detect Main office, Restroom26 103 9/18/24 ND Non-Detect Main office, Heath room 13, nurse faucet 104 9/18/24 0.315 Low Restroom 13A, bathroom faucet 105 9/18/24 0.498 Low Gym building, west water bottle filler 106 9/18/24 ND Non-Detect Gym building, weight room 107 9/18/24 ND Non-Detect Gym building, east water bottle filler 108 9/18/24 ND Non-Detect Gym building, North entrance, men restroom, bathroom faucet, left 109 9/18/24 0.506 Low Gym building, North entrance, men restroom, bathroom faucet, right 110 9/18/24 0.626 Low Gym building, North entrance, women restroom, bathroom faucet, left 111 9/18/24 ND Non-Detect Gym building, North entrance, women restroom, bathroom faucet, right 112 9/18/24 0.228 Low Gym building, out of north restroom, water bottle filler 113 9/18/24 ND Non-Detect Gym building, women locker room, coach room, bathroom faucet, left 114 9/18/24 12.6 High Gym building, women locker room, coach room, bathroom faucet, right 115 9/18/24 5.94 Low Gym building, women locker room, water bottle filler 116 9/18/24 ND Non-Detect Gym building, women locker room, southeast bathroom faucet, left 117 9/18/24 0.350 Low Gym building, women locker room, southeast bathroom faucet, right 118 9/18/24 0.406 Low Gym building, women locker room, northwest bathroom faucet, left 119 9/18/24 0.361 Low Gym building, women locker room, northwest bathroom faucet, right 120 9/18/24 0.359 Low Gym building, women locker room, northwest water bottle filler 121 9/18/24 ND Non-Detect Gym building, men locker room, northwest 122 9/18/24 Not Tested - Gym building, men locker room, northwest bathroom faucet 123 9/18/24 0.277 Low Gym building, men locker room, west bathroom faucet, left 124 9/18/24 0.346 Low Gym building, men locker room, west bathroom faucet, right 125 9/18/24 ND Non-Detect Gym building, men locker room, west water bottle filler 126 9/18/24 2.64 Low Gym building, men locker room, coach room, bathroom faucet 127 9/18/24 0.246 Low Restroom 87, bathroom faucet 128 9/18/24 ND Non-Detect Restroom 89, bathroom faucet 129 9/18/24 0.359 Low Room 215, staff sink faucet 130 9/18/24 ND Non-Detect Art building, band room A15, classroom faucet 131 9/18/24 0.387 Low Art building, choir room A14, classroom faucet 132 9/18/24 0.385 Low Art building, dark room in classroom A13 133 9/18/24 0.881 Low Art building, classroom A11, classroom faucet 134 9/18/24 8.17 Moderate Art building, classroom A11, drinking fountain 135 9/18/24 6.38 Low Art building, west men restroom, bathroom faucet, left 136 9/18/24 0.362 Low Art building, west men restroom, bathroom faucet, left center 137 9/18/24 0.840 Low Art building, west men restroom, bathroom faucet, center 138 9/18/24 0.441 Low Art building, west men restroom, bathroom faucet, right center 139 9/18/24 1.23 Low Art building, west men restroom, bathroom faucet, right 140 9/18/24 1.22 Low Art building, west men restroom, bathroom faucet, right next to wall 141 9/18/24 0.772 Low Art building, west women restroom, bathroom faucet, left 142 9/18/24 0.596 Low Art building, west women restroom, bathroom faucet, left center 143 9/18/24 0.724 Low Art building, west women restroom, bathroom faucet, center 144 9/18/24 0.518 Low Art building, west women restroom, bathroom faucet, right center 145 9/18/24 0.506 Low Art building, west women restroom, bathroom faucet, right 146 9/18/24 0.533 Low Art building, west women restroom, bathroom faucet, right next to wall 147 9/18/24 0.682 Low Art building, concession room, kitchen sink 148 9/18/24 ND Non-Detect Art building, hallway out of theater, water bottle filler 149 9/18/24 ND Non-Detect Art building, black box room, dressing room, classroom sink faucet, North 150 9/18/24 3.06 Low Art building, black box room, dressing room, classroom sink faucet, Northeast 151 9/18/24 1.44 Low Art building, black box room, dressing room, classroom sink faucet, Southeast 152 9/18/24 3.72 Low Art building, black box room, dressing room, classroom sink faucet, South 153 9/18/24 1.36 Low Art building, black box room, dressing room, men bathroom faucet, left 154 9/18/24 2.26 Low Art building, black box room, dressing room, men bathroom faucet, right 155 9/18/24 3.76 Low Art building, black box room, dressing room, women bathroom faucet, left 156 9/18/24 0.327 Low Art building, black box room, dressing room, women bathroom faucet, right 157 9/18/24 1.06 Low Art building, wood shop, drinking fountain 158 9/18/24 0.456 Low Art building, 2nd floor, hall out of elevator 159 9/18/24 ND Non-Detect Art building, 2nd floor, room A21, classroom faucet, left 160 9/18/24 1.09 Low Art building, 2nd floor, room A21, classroom faucet, right 161 9/18/24 3.21 Low Art building, 2nd floor, Hall out of room A23 162 9/18/24 0.670 Low Art building, 2nd floor, classroom A23, classroom faucet, left 163 9/18/24 0.976 Low Art building, 2nd floor, classroom A23, classroom faucet, right 164 9/18/24 0.330 Low Art building, 2nd floor, classroom A22, classroom faucet, left 165 9/18/24 1.62 Low Art building, 2nd floor, classroom A22, classroom faucet, middle 166 9/18/24 Not Tested - Art building, 2nd floor, classroom A22, classroom faucet, right 167 9/18/24 3.69 Low Art building, 2nd floor, restroom faucet next to classroom A22 168 9/18/24 0.436 Low Exterior building, outside spigot, classroom 520, southwest exterior wall 169 9/18/24 41.2 Action Req. Exterior building, outside spigot, classroom 513, south exterior wall 170 9/18/24 630 Action Req. Exterior building, outside spigot, classroom 713, south exterior wall 171 9/18/24 19.4 Action Req. Exterior building, outside spigot, classroom 720, south exterior wall 172 9/18/24 84.7 Action Req. Exterior building, outside spigot, men locker room, southeast exterior wall 173 9/18/24 5.34 Low Room 201, Staff lounge, staff faucet 174 9/18/24 0.629 Low Room 518, classroom faucet, left 175 9/18/24 2.12 Low Room 518, classroom faucet, right 176 9/18/24 1.14 Low Room 520, classroom faucet, left 177 9/18/24 3.18 Low Room 520, classroom faucet, right 178 9/18/24 2.07 Low Room 519, classroom faucet, left 179 9/18/24 0.785 Low Room 519, classroom faucet, right 180 9/18/24 0.913 Low Room 517, classroom faucet, left 181 9/18/24 0.565 Low Room 517, classroom faucet, right 182 9/18/24 0.478 Low Gym building, Northwest of main entrance 183 9/18/24 257 Action Req. Fixtures Not Tested
The fixtures listed “Not Tested” could not be sampled by PBS, as they were either shut off or inaccessible. PBS assigned them a number in sequence so they can be sampled later if they are brought back online.
-
On September 24, 2024, PBS Engineering and Environmental Inc. (PBS) performed drinking water sampling and analysis for lead at Reynolds Learning Academy in Fairview, Oregon. The testing was requested by Reynolds School District to meet requirements from the Oregon Department of Education (ODE) and Oregon Health Authority (OHA) to conduct testing for lead in school drinking water systems.
Initial Test Results


Lead in Water Test Notes
- The lead in water Action Level is 15 parts per billion (ppb).
- Any fixture testing at or above the action level of 15 ppb is immediately removed from service and cannot be returned to service until it has been remediated and passed follow-up testing.
- A "ND" or "non-detect" test result indicates the sample measu
- Test results equal to or greater than the Action Level of 15 ppb are highlighted in red and precede a "High" value.
- Test results near the Action Level of 15 ppb (11.99 to 14.99 ppb) are highlighted in yellow and precede a "Med" (Medium) value.
-
On September 20, 2024, PBS Engineering and Environmental Inc. (PBS) performed drinking water sampling and analysis for lead at Edgefield Campus, building A, G, H, I, J in Troutdale, Oregon. The testing was requested by Reynolds School District to meet requirements from the Oregon Department of Education (ODE) and Oregon Health Authority (OHA) to conduct testing for lead in school drinking water systems.

Lead in Water Test Notes
- The lead in water Action Level is 15 parts per billion (ppb).
- Any fixture testing at or above the action level of 15 ppb is immediately removed from service and cannot be returned to service until it has been remediated and passed follow-up testing.
- A "ND" or "non-detect" test result indicates the sample measured below the minimum detection limit of [#] ppb.
- Test results equal to or greater than the Action Level of 15 ppb are highlighted in red and precede a "High" value.
- Test results near the Action Level of 15 ppb (11.99 to 14.99 ppb) are highlighted in yellow and precede a "Med" (Medium) value.
-
On October 31, 2024, PBS Engineering and Environmental Inc. (PBS) performed drinking water sampling and analysis for lead at Transportation Building A, B, C in Portland, Oregon. The testing was requested by Reynolds School District (the District) to meet requirements from the Oregon Department of Education (ODE) and Oregon Health Authority (OHA) to conduct testing for lead in school drinking water systems.
Initial Test Results

Lead in Water Test Notes
- The lead in water Action Level is 15 parts per billion (ppb).
- Any fixture testing at or above the action level of 15 ppb is immediately removed from service and cannot be returned to service until it has been remediated and passed follow-up testing.
- A "ND" or "non-detect" test result indicates the sample measured below the minimum detection limit of [#] ppb.
- Test results equal to or greater than the Action Level of 15 ppb are highlighted in red and precede a "High" value.
- Test results near the Action Level of 15 ppb (11.99 to 14.99 ppb) are highlighted in yellow and precede a "Med" (Medium) value.
-
On October 30, 2024, PBS Engineering and Environmental Inc. (PBS) performed drinking water sampling and analysis for lead at Reynolds School District Warehouses in Portland, Oregon. The testing was requested by Reynolds School District to meet requirements from the Oregon Department of Education (ODE) and Oregon Health Authority (OHA) to conduct testing for lead in school drinking water systems.
Initial Test Results

Lead in Water Test Notes
- The lead in water Action Level is 15 parts per billion (ppb).
- Any fixture testing at or above the action level of 15 ppb is immediately removed from service and cannot be returned to service until it has been remediated and passed follow-up testing.
- A "ND" or "non-detect" test result indicates the sample measured below the minimum detection limit of [#] ppb.
- Test results equal to or greater than the Action Level of 15 ppb are highlighted in red and precede a "High" value.
- Test results near the Action Level of 15 ppb (11.99 to 14.99 ppb) are highlighted in yellow and precede a "Med" (Medium) value.
-
On October 30 2024, PBS Engineering and Environmental Inc. (PBS) performed drinking water sampling and analysis for lead at Reynolds School District Office in Fairview, Oregon. The testing was requested by Reynolds School District to meet requirements from the Oregon Department of Education (ODE) and Oregon Health Authority (OHA) to conduct testing for lead in school drinking water systems.

Lead in Water Test Notes
- The lead in water Action Level is 15 parts per billion (ppb).
- Any fixture testing at or above the action level of 15 ppb is immediately removed from service and cannot be returned to service until it has been remediated and passed follow-up testing.
- A "ND" or "non-detect" test result indicates the sample measured below the minimum detection limit of [#] ppb.
- Test results equal to or greater than the Action Level of 15 ppb are highlighted in red and precede a "High" value.
- Test results near the Action Level of 15 ppb (11.99 to 14.99 ppb) are highlighted in yellow and precede a "Med" (Medium) value.
-
On October 1, 2024, PBS Engineering and Environmental Inc. (PBS) performed drinking water sampling and analysis for lead at HOLLA School in Portland, Oregon. The testing was requested by Reynolds School District to meet requirements from the Oregon Department of Education (ODE) and Oregon Health Authority (OHA) to conduct testing for lead in school drinking water systems.

Lead in Water Test Notes
- The lead in water Action Level is 15 parts per billion (ppb).
- Any fixture testing at or above the action level of 15 ppb is immediately removed from service and cannot be returned to service until it has been remediated and passed follow-up testing.
- A "ND" or "non-detect" test result indicates the sample measured below the minimum detection limit of [#] ppb.
- Test results equal to or greater than the Action Level of 15 ppb are highlighted in red and precede a "High" value.
- Test results near the Action Level of 15 ppb (11.99 to 14.99 ppb) are highlighted in yellow and precede a "Med" (Medium) value.
2022-23 Testing
-
In May 2023, PBS Engineering and Environmental Inc. (PBS) performed drinking water sampling and analysis for lead at Glenfair Elementary School in Portland, Oregon. The testing was requested by Reynolds School District to meet requirements from the Oregon Department of Education (ODE) and Oregon Health Authority (OHA) to conduct testing for lead in school drinking water systems.
Lead in Water Test Notes
- The lead in water Action Level is 15 parts per billion (ppb).
- Any fixture testing at or above the action level of 15 ppb is immediately removed from service and cannot be returned to service until it has been remediated and passed follow-up testing.
- A "ND" or "non-detect" test result indicates no lead.
- Test results equal to or greater than the Action Level of 15 ppb are highlighted in red and precede a "Action Required" value.
- Test results near the Action Level of 15 ppb (12 to 14.99 ppb) are highlighted in orange and precede a "High" value.
Test Results
Fixture Location Description Fixture ID # Initial
Test DateInitial Test Result (ppb) Initial
LevelKitchen, SW corner 001 5/1/23 2.4 Low Kitchen, staff restroom 002 5/1/23 3.32 Low Kitchen, north wall 003 5/1/23 0.57 Low Cafeteria 004 5/1/23 ND Non-Detect Cafeteria 005 5/1/23 ND Non-Detect Room 16 east restroom 006 5/1/23 11.20 Moderate Room 16 workroom 007 5/1/23 3.950 Low Room 16 workroom 008 5/1/23 0.9 Low Room 16 west restroom 009 5/1/23 3.92 Low Room 17 west restroom 010 5/1/23 2.420 Low Room 17 workroom 011 5/1/23 9.42 Moderate Room 17 workroom 012 5/1/23 2.84 Low Room 17 east restroom 013 5/1/23 4.61 Low Room 19 east restroom 014 5/1/23 2.27 Low Room 19 workroom 015 5/1/23 4.82 Low Room 19 workroom 016 5/1/23 1.590 Low Room 19 west restroom 017 5/1/23 1.590 Low Room 14 west restroom 018 5/1/23 1.72 Low Room 14 019 5/1/23 2.31 Low Room 14 020 5/1/23 1.27 Low Room 14 east restroom 021 5/1/23 1.02 Low Library 022 5/1/23 6.59 Low Library 023 5/1/23 0.81 Low Room 20 024 5/1/23 10.10 Moderate Room 20 025 5/1/23 2.12 Low West hall, north 026 5/1/23 ND Non-Detect West hall, north 027 5/1/23 ND Non-Detect Room 12 restroom 028 5/1/23 1.72 Low Room 12 029 5/1/23 2.09 Low Room 12 030 5/1/23 1.190 Low Room 12 east restroom 031 5/1/23 1.400 Low West hall, west leg boy’s restroom 032 5/1/23 2.41 Low West hall, west leg boy’s restroom 033 5/1/23 1.68 Low West hall, west leg faculty restroom 034 5/1/23 0.557 Low West hall, west leg faculty restroom 035 5/1/23 1.56 Low West hall, west leg room 23 restroom 036 5/1/23 14.60 High Gym 037 5/1/23 ND Non-Detect Gym 038 5/1/23 ND Non-Detect Room 11 039 5/1/23 11.20 Moderate East hall boy’s restroom 040 5/1/23 0.39 Low East hall boy’s restroom 041 5/1/23 ND Non-Detect East hall boy’s restroom 042 5/1/23 0.38 Low Eaast hall girl's restroom 043 5/1/23 Not Tested - East hall girl’s restroom 044 5/1/23 ND Non-Detect East hall, west 045 5/1/23 ND Non-Detect East hall, west 046 5/1/23 ND Non-Detect East hall, west drinking fountain 047 5/1/23 Not Tested - Room 10 048 5/1/23 2.050 Low Room 10 049 5/1/23 3.49 Low Room 9 050 5/1/23 1.51 Low Room 9 051 5/1/23 1.35 Low Room 8 052 5/1/23 3.74 Low Room 8 053 5/1/23 2.07 Low Room 7 054 5/1/23 8.46 Moderate Room 7 055 5/1/23 0.84 Low East hall basement classroom 056 5/1/23 0.60 Low East hall basement classroom 057 5/1/23 0.35 Low East hall basement classroom restroom 058 5/1/23 0.899 Low East hall basement classroom restroom 059 5/1/23 1.230 Low East hall basement classroom 060 5/1/23 0.78 Low East hall basement classroom 061 5/1/23 0.209 Low Room 6 062 5/1/23 6.880 Low Room 6 063 5/1/23 2.220 Low Room 5 064 5/1/23 7.11 Low Room 5 065 5/1/23 2.42 Low Room 4 066 5/1/23 3.670 Low Room 4 067 5/1/23 0.58 Low Room 3 068 5/1/23 6.75 Low Room 3 069 5/1/23 2.0 Low Room 2 070 5/1/23 5.430 Low Room 2 071 5/1/23 2.52 Low Teachers lounge 072 5/1/23 0.96 Low Teachers lounge 073 5/1/23 ND Non-Detect Nurses office restroom 074 5/1/23 1.46 Low